Setting the data rate – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 31

Advertising
background image

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

31

Configuring the Adapter

Chapter 3

2.

Set the value of Parameters 42 - [Subnet Cfg 1] through 45 - [Subnet
Cfg 4]

to the desired value for the subnet mask.

3.

Reset the adapter by power cycling the drive or by using the HIM’s Reset
Device function located in the drive’s DIAGNOSTIC folder.

Set the Gateway Address

1.

Verify that Parameter 36 - [BOOTP] is set to ‘0’ (Disabled).

2.

Set the value of Parameters 46 - [Gateway Cfg 1] through 49 - [Gateway
Cfg 4]

to the IP address of the gateway device.

3.

Reset the adapter by power cycling the drive or by using the HIM’s Reset
Device function located in the drive’s DIAGNOSTIC folder.

Setting the Data Rate

By default, the adapter is set to autodetect, so it automatically detects the data
rate and duplex setting used on the network. If you need to set a specific data rate
and duplex setting, the value of Parameter 50 - [Net Rate Cfg] determines the
Ethernet data rate and duplex setting that the adapter will use to communicate.
For definitions of data rate and duplex, see the

Glossary

.

1.

Set the value of Parameter 50 - [Net Rate Cfg] to the data rate at which
your network is operating.

Default = 0.0.0.0

255.255.255.255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

Edit Subnet Cfg 1

0

0 << 255

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Default = 0.0.0.0

255.255.255.255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]

Edit Gateway Cfg 1

0

0 << 255

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Value

Data Rate

0

Autodetect (default)

1

10 Mbps Full

2

10 Mbps Half

3

100 Mbps Full

4

100 Mbps Half

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Net Rate Cfg

Autodetect

0

0 << 4