Operating Instructions – MOVIMOT® MM03C - MM3XC

8

Startup procedure

Startup with Integrated AS-Interface

8.6

Startup procedure

1. Isolate MOVIMOT

®

drive from the supply, safeguarding it against unintentional

power-up! Dangerous voltages may still be present for up to 1 minute after
shutdown!

2. With mounted MOVIMOT

®

inverter and switch S5 = 1 (factory setting), set the de-

sired AS-i address either via a hand-held programming device (see page 103) or lat-
er via a master (see the description of your AS-i master).

3. Review correct connection of MOVIMOT

®

(see the section "Electrical Installa-

tion").

4. Set the type of 24 V supply with switch S5 (see page 104).

5. Set the first speed with setpoint potentiometer f1 (factory setting approx. 50 Hz).

6. Set the second speed with switch f2 (active when AS-i bit "speed f1/speed f2" = "1").

7. Set the ramp time with switch t1. (The ramp times are in relation to a setpoint step

change of 50 Hz.)

8. Place the MOVIMOT

®

inverter on the terminal box and secure it.

9. Re-insert screw plug of setpoint potentiometer f1 with gasket.

10. Switch on AS-i voltage, 24 V auxiliary voltage and supply voltage.

05066BXX

[1] Pot. position

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

Setpoint f2 [Hz]

5

7

10

15

20

25

35

50

60

70

100

1

2

3

4

5

6

7

8

9

10

0

100

f [Hz

[1]

]

2

75

25

50

6

5

f

1

3

4

5
6

7

8

During operation, the first speed is infinitely variable using the setpoint potenti-
ometer f1 which is accessible from outside.

Speeds f1 and f2 can be set independently to any value.

Switch t1

Detent position

0

1

2

3

4

5

6

7

8

9

10

Ramp time t1 [s]

0.1

0.2

0.3

0.5

0.7

1

2

3

5

7

10

3

4

5
6

7

8

0

0

I