Dip switches     s1/6, Dip switches     s1/7, Dip switches     s1/8 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 54

Advertising
background image

54

Operating Instructions – MOVIMOT® MM03C - MM3XC

7

Description of the DIP switches S1

Startup of Standard Design

DIP switches
S1/6

Motor rating class smaller

If it is activated, the DIP switch enables the assignment of MOVIMOT

®

to a motor

with a smaller rating class. The rated power of the unit remains unchanged.

If a motor with less power is used, the overload capacity of the drive may increase
since the motor considers the MOVIMOT

®

to be one power increment too high. A

larger current may be impressed for a short period of time, which results in higher
torques.

The purpose of switch S1/6 is the short-term utilization of the motor peak torque. The
current limit of the respective unit is always the same, independent of the switch set-
ting. The motor protection function is adapted in reference to the switch setting.

In this operating mode with S1/6 = "ON", a pull-out protection of the motor is
not possible.

DIP switches
S1/7

Setting the maximum PWM frequency

With setting DIP SWITCH S1/7 = OFF, MOVIMOT

®

operates with 4 kHz PWM fre-

quency.

With setting DIP SWITCH S1/7 = ON, MOVIMOT

®

operates with a 16 kHz PWM fre-

quency (low noise) and switches back in steps to lower switching frequencies de-
pending on the heat sink temperature.

DIP switches
S1/8

No-load damping function (S1/8 = ON)

Upon activation, the function prevents resonant oscillations in no-load operation.

MOVIMOT

®

inverter

Assigned motor

S1/6 = OFF

S1/6 = ON

Ħ

Ħ

MM03

DT71D4

DR63L4

1)

DR63L4

1)

MM05

DT80K4

DT71D4

DT71D4

DFR63L4

1)

1) Only possible with offset assembly

MM07

DT80N4

DT80K4

DT80K4

DT71D4

MM11

DT90S4

DT80N4

DT80N4

DT80K4

MM15

DT90L4

DT90S4

DT90S4

DT80N4

MM22

DV100M4

DT90L4

DT90L4

DT90S4

MM30

DV100L4

DV100M4

DV100M4

DT90L4

MM3X

DV100L4

DV100L4

DV100M4

0

0

I