Operating Instructions – MOVIMOT® MM03C - MM3XC

8

Important startup instructions

Startup with Integrated AS-Interface

8

Startup with Integrated AS-Interface

8.1

Important startup instructions

It is essential to comply with the safety notes during installation!

Before removing/attaching the MOVIMOT

®

inverter, it must be disconnected

from the power supply system (mains). Dangerous voltages may still be
present for up to 1 minute after shutdown.

Ensure before startup that the drive has not been damaged.

Check that all protective covers are installed correctly.

A minimum switch-off time of 2 seconds must be maintained for the mains contactor
K11.

8.2

Description of the controls

Setpoint potenti-
ometer f1

The potentiometer is used to adjust setpoint f1:

Setpoint f1 is selected via the AS-i bit "speed f1/speed f2".

Setpoint switch f2

The switch is used to adjust setpoint f2:

Setpoint f2 is selected via the AS-i bit "speed f1/speed f2".

Switch t1

For integrator ramp (ramp times based on a setpoint jump of 50 Hz)

05066BXX

[1] Pot. position

1

2

3

4

5

6

7

8

9

10

0

100

f [Hz

[1]

]

2

75

25

50

6

5

f

1

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

Setpoint f2 [Hz]

5

7

10

15

20

25

35

50

60

70

100

3

4

5
6

7

8

Switch t1

Detent position

0

1

2

3

4

5

6

7

8

9

10

Ramp time t1 [s]

0.1

0.2

0.3

0.5

0.7

1

2

3

5

7

10

3

4

5
6

7

8

0

0

I