Protection devices, Ul compliant installation – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 38

Advertising
background image

38

Operating Instructions – MOVIMOT® MM03C - MM3XC

6

Installation instructions

Electrical Installation with Integrated AS-Interface

Protection
devices

MOVIMOT

®

drives are equipped with integrated protective overload devices that are

making external overload devices obsolete.

UL compliant
installation

Use only copper cables with the temperature range 60 / 75 °C.

The permitted tightening torques for MOVIMOT

®

power terminals are:

– 1.5 Nm (13.3 lb.in).

MOVIMOT

®

are suited for operation on voltage supply systems with grounded star

(TN and TT systems) supplying a maximum supply current of 5000 A

AC

and having

a maximum rated voltage of 500 V

AC

(MM03C-503 to MM3XC-503). The perfor-

mance data of the fuses must not exceed 35 A/600 V.

Only use tested units with a limited output voltage (V

max

= 30 V

DC

) and limited output

current (I

8 A) as an external 24 V

DC

voltage source.

UL certification applies only to operation in voltage supply systems with voltages to
ground up to 300 V.