9 startup with communications interface / fieldbus, 1 startup procedure, Startup procedure – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 117: 9startup with communications interface / fieldbus

Advertising
background image

Operating Instructions – MOVIMOT® MM03C - MM3XC

117

9

Startup procedure

Startup with Communications Interface / Fieldbus

9

Startup with Communications Interface / Fieldbus

9.1

Startup procedure

1. Review correct connection of MOVIMOT

®

(see the section "Electrical Installa-

tion").

2. Set the correct RS-485 address on DIP switches S1/1...S1/4. Always set address

"1" in conjunction with SEW fieldbus interfaces (MF...).

3. Set the minimum frequency f

min

with switch f2.

4. If ramp is not set via fieldbus, set ramp time with switch t1 (ramp times are based on

a setpoint jump of 50 Hz).

5. Check whether the required direction of rotation is enabled.

Decimal
address

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

S1/1

X

X

X

X

X

X

X

X

S1/2

X

X

X

X

X

X

X

X

S1/3

X

X

X

X

X

X

X

X

S1/4

X

X

X

X

X

X

X

X

X

= ON

=

OFF

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

Minimum frequency f

min

[Hz]

2

5

7

10

12

15

20

25

30

35

40

Switch t1

Detent position

0

1

2

3

4

5

6

7

8

9

10

Ramp time t1 [s]

0.1

0.2

0.3

0.5

0.7

1

2

3

5

7

10

Terminal R

Terminal L

Message

Activated

Activated

Both directions of rotation are enabled

Activated

Not activated

Only clockwise direction of rotation is enabled

Preselected setpoints for counterclockwise rotation result in
standstill of drive

Not activated

Activated

Only counterclockwise direction of rotation is enabled

Setpoint selections for clockwise lead to the drive being
stopped

Not activated

Not activated

Unit is blocked or the drive is stopped

3

4

5
6

7

8

3

4

5
6

7

8

24V

R

L

24V

R

L

24V

R

L

24V

R

L

0

0

I