Startup with mwa21a option (speed control module) – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 82

Advertising
background image

82

Operating Instructions – MOVIMOT® MM03C - MM3XC

7

Startup with MWA21A option (speed control module)

Startup of Standard Design

7.8

Startup with MWA21A option (speed control module)

1. Isolate MOVIMOT

®

drive from the supply, safeguarding it against unintentional

power-up! Dangerous voltages may still be present for up to 1 minute after
shutdown!

2. Review correct connection of MOVIMOT

®

(see the section "Electrical Installa-

tion").

3. Set DIP switch S1/1 (on MOVIMOT

®

) to ON (= address 1).

4. Set the minimum frequency f

min

with switch f2.

5. Set the ramp time with switch t1 (ramp times in relation to a setpoint step change of

50 Hz).

6. Check whether the required direction of rotation is enabled.

05064AXX

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

Minimum frequency f

min

[Hz]

2

5

7

10

12

15

20

25

30

35

40

Switch t1

Detent position

0

1

2

3

4

5

6

7

8

9

10

Ramp time t1 [s]

0.1

0.2

0.3

0.5

0.7

1

2

3

5

7

10

Terminal R

Terminal L

Message

Activated

Activated

Both directions of rotation are enabled

Activated

Not activated

Only clockwise direction of rotation is enabled

Preselected setpoints for counterclockwise rotation result in
standstill of drive

Not activated

Activated

Only counterclockwise direction of rotation is enabled

Setpoint selections for clockwise lead to the drive being
stopped

Not activated

Not activated

Unit is blocked or the drive is stopped

1

ON

6

7

8

5

4

3

2

1

ON

2

3

4

5
6

7

8

3

4

5
6

7

8

24V

R

L

24V

R

L

24V

R

L

24V

R

L

0

0

I