Connecting sup-
ply system leads

The rated voltage and frequency of MOVIMOT

®

must correspond to the data for the

power supply system (mains).

Cable cross section: according to input current I

mains

for rated power (see Technical

Data).

Permitted cable cross section of MOVIMOT

®

terminals (does not apply to field dis-

tributor)

Use conductor end sleeves without insulating shrouds (DIN 46228 part 1, material
E-CU).

Install line safety at the beginning of the power cable behind supply bus junction (see
the section "Connection of MOVIMOT

®

basic unit," F11/F12/F13). Use D, DO, NH or

circuit breakers. The fusible rating should be selected in accordance with the cable
cross section.

Do not use a conventional earth-leakage circuit breaker as a protective device. Uni-
versal current-sensitive earth leakage circuit-breakers (tripping current 300 mA) are
permitted as a protective device. During normal operation of MOVIMOT

®

, earth-leak-

age currents of > 3.5 mA can occur.

Use contactor switch contacts to switch MOVIMOT

®

from utilization category AC-3

according to IEC 158.

SEW recommends using earth-leakage monitors with pulse-code measurement for
voltage supply systems with non-grounded star point (IT nets). The use of such de-
vices avoids mis-tripping of the earth-leakage monitor due to the earth capacitance
of the inverter.

Installation at
1000 meters
above sea level
(msl)

MOVIMOT

®

drives with supply voltages of 380 to 500 V can be used at altitudes above

2000 m MSL up to 4000 m MSL under the following peripheral conditions.

1)

The rated continuous power is reduced based on the reduced cooling above 1000 m
(see the section "Technical Data and Dimension Drawings").

Above 2000 msl, the air and creeping distances are only sufficient for overvoltage
class 2. If the installation requires overvoltage class 3, an additional external over-
voltage protection must be used to ensure that overvoltage surges are limited to
2.5 kV phase-to-phase and phase-to-ground.

If safe electrical separation is required, it must be implemented outside the device at
altitudes above 2000 m MSL (Safe Electrical Separation in accordance with
EN 50178).

The permitted rated supply voltage of 3 x 500 V up to 2000 msl is reduced by 6 V for
every 100 m to a maximum of 3 x 380 V at 4000 msl.

Power terminals

Control terminals

1.0 mm

2

– 4.0 mm

2

(2 x 4.0 mm

2

)

0.25 mm

2

– 1.0 mm

2

(2 x 0.75 mm

2

)

AWG17 – AWG10 (2 x AWG10)

AWG22 – AWG17 (2 x AWG18)

1) The maximum altitude is limited by creeping distances and flameproof components such as electrolytic

capacitors.