Special function 5 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 64

Advertising
background image

64

Operating Instructions – MOVIMOT® MM03C - MM3XC

7

Selectable special functions MM..C-503-00

Startup of Standard Design

Special function 5

MOVIMOT

®

motor protection via TH

Function descrip-
tion

Functions in connection with fieldbus interfaces MF.. and MQ..:

If both direction of rotation terminals are opened, special function 5 generates fault
84 (overtemperature motor).

In conjunction with the mounting of the MOVIMOT

®

inverter close to the motor (with

option P2.A or in the field distributor), the direction of rotation terminals are set to "0"
by the TH in case of overtemperature in the motor.

Fault 84 is displayed by means of a flashing signal of the status LED at MOVIMOT

®

.

The generated fault 84 is also transmitted via fieldbus.

Functions in connection with fieldbus interfaces MQ..:

MOVIMOT

®

bus parameter setting according to special function 4 (see page 62).

Functions in connection with fieldbus interfaces MF..:

Potentiometer f1 and switches f2 and t1 are deactivated and the following values
apply:

05600AXX

1

6

7

8

5

4

3

2

ON

S2

6

7

8

5

The special function is only intended for bus operation in conjunction with mount-
ing of the MOVIMOT

®

inverter close to the motor (with option P2.A or in the field

distributor).

Name

Value

Ramp up

1 [s]

Ramp down

1 [s]

Minimum frequency

2 [Hz]

Maximum frequency

100 [Hz]

Current limit

160 [%]

Pre-magnetization time

0.4 [s]

Post-magnetization time

0.1 [s]

Delay time speed monitoring

1 [s]

Brake release time

0 [s]

Slip compensation

Rated motor slip

0

0

I

Advertising