Special function 3 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 60

Advertising
background image

60

Operating Instructions – MOVIMOT® MM03C - MM3XC

7

Selectable special functions MM..C-503-00

Startup of Standard Design

Special function 3

MOVIMOT

®

with adjustable current limitation (switchable via terminal f1/f2), with

reduction of frequency if exceeded

Function descrip-
tion

The current limitation can be set via switch f2. The binary input terminal f1/f2 can be
used to toggle between maximum current limit and the current limitation set via switch f2.

Response after
reaching the cur-
rent limitation

After reaching the current limit, the unit reduces the frequency using the current lim-
itation function and if necessary stops the ramp to prevent the current from increas-
ing.

If the unit operates at the current limitation, the status is displayed through rapid
green flashing of the status LED.

In-system values
for setpoint f2/mini-
mum frequency

It is no longer possible to toggle via terminals between setpoint f1 and setpoint f2 in
terminal operation or to set the minimum frequency in bus operation.

The minimum frequency in bus operation is fixed at 2 Hz.

Adjustable current
limits


Selection of cur-
rent limits via
binary input termi-
nal f1/f2

05598AXX

1

6

7

8

5

4

3

2

ON

S2

6

7

8

5

3

4

5
6

7

8

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

I

max

[%] of I

N

60

70

80

90

100

110

120

130

140

150

160

03819AXX

f1/f2 = "0"

160 % current limitation is active

03820AXX

f1/f2 = "1"

The current limitation set via switch f2 is active.
The selection can also be made with enabled unit.

R

L

24V

f1/f2

R

L

24V

f1/f2

0

0

I

Advertising