Operating Instructions – MOVIMOT® MM03C - MM3XC

89

7

Additional information for mounting close to the motor

Startup of Standard Design

DIP switch

With mounting of the MOVIMOT

®

inverter close to the motor, set DIP switch S1/5 to ON

which is different than the factory setting.

Braking resistor

With motors without brakes, an internal braking resistor (BW1 or BW2) must be con-
nected to the MOVIMOT

®

.

With brake motors, no braking resistor may be connected to the MOVIMOT

®

.

Mounting of the
MOVIMOT

®

inverter in the
field distributor

Observe the instructions in the corresponding manuals when mounting the MOVIMOT

®

inverter close to the motor in the field distributor:

PROFIBUS Interfaces, Field Distributors

InterBus Interfaces, Field Distributors

DeviceNet/CANopen Interfaces, Field Distributors

AS-Interfaces, AS-i field distributors

S1

1

2

3

4

5

Motor

protec-

tion

6

Motor

rating class

7

PWM

frequency

8

No-load

damping

Message

RS-485 address

2

0

2

1

2

2

2

3

ON

1

1

1

1

Off

Motor one

size smaller

Variable

(16, 8, 4 kHz)

On

OFF

0

0

0

0

On

adapted

4 kHz

Off

06487AXX

13

14

15

BW1 / BW

2

MOVIMOT

®

0

0

I