Operating Instructions – MOVIMOT® MM03C - MM3XC

77

7

Startup with binary control (control via terminals)

Startup of Standard Design

7.6

Startup with binary control (control via terminals)

1. Isolate MOVIMOT

®

drive from the supply, safeguarding it against unintentional

power-up! Dangerous voltages may still be present for up to 1 minute after
shutdown!

2. Review correct connection of MOVIMOT

®

(see the section "Electrical Installa-

tion").

3. Ensure that DIP switches S1/1 – S1/4 are set to OFF (= address 0).

4. Set first speed with f1 setpoint potentiometer (activated if terminal f1/f2 = '0') (factory

setting: approx. 50 Hz).

5. Set the second speed with switch f2 (active when tl. f1/f2 = "1").

6. Set the ramp time with switch t1 (ramp times in relation to a setpoint step change of

50 Hz).

7. Place the MOVIMOT

®

inverter on the terminal box and secure it.

8. Re-insert screw plug of setpoint potentiometer f1 with gasket.

9. Switch on the control voltage 24 V

DC

and power supply.

05062AXX

05066BXX

[1] Pot. position

Switch f2

Detent position

0

1

2

3

4

5

6

7

8

9

10

Setpoint f2 [Hz]

5

7

10

15

20

25

35

50

60

70

100

1

ON

6

7

8

5

4

3

2

1

ON

4

3

2

1

2

3

4

5

6

7

8

9

10

0

100

f [Hz

[1]

]

2

75

25

50

6

5

f

1

3

4

5
6

7

8

During operation, the first speed is infinitely variable using the setpoint potenti-
ometer f1 which is accessible from outside.

Speeds f1 and f2 can be set independently to any value.

Switch t1

Detent position

0

1

2

3

4

5

6

7

8

9

10

Ramp time t1 [s]