Address (adr), Group address, User data type (type) – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 123: Timeout monitoring

Advertising
background image

Operating Instructions – MOVIMOT® MM03C - MM3XC

123

9

Function with RS-485 master

Startup with Communications Interface / Fieldbus

Start pause (idle)
and start charac-
ter (start delim-
iter)

MOVIMOT

®

detects the start of a request message by means of a start pause lasting at

least 3.44 ms, followed by the character 02

hex

(start delimiter 1). In the event that the

transmission of a valid request message is broken off by the master, a new request mes-
sage may not be sent until at least twice the start pause (approx. 6.88 ms) has elapsed.

Address (ADR)

MOVIMOT

®

supports the address range from 0 to 15 and access via the point-to-point

address (254) or via the broadcast address (255). It is only possible to read the current
process input data (status word, current actual value) via address 0. The output data
sent by the master do not come into effect because PO data processing is not active
when the address setting is 0.

Group address

Furthermore, ADR = 101...115 makes it possible to group together several MOVIMOT

®

units. When this is done, all MOVIMOT

®

units in one group are set to the same RS-485

address (e.g. group 1: ADR = 1, group 2: ADR = 2).

The master can now specify new group setpoints for these groups using ADR = 101 (set-
points to inverters of group 1) and ADR = 102 (setpoints to group 2). The inverters do
not send any response when this addressing variant is used. The master must observe
a rest time of min. 25 ms between two broadcast or group messages.

User data type
(TYPE)

MOVIMOT

®

always supports four different PDU types (Protocol Data Unit). These are

largely determined by the process data length and type of transmission.

Timeout monitor-
ing

In "cyclical" transmission, MOVIMOT

®

expects the next bus activity (request message

of the aforementioned types) within one second at most. If this bus activity is not detect-
ed, the drive automatically decelerates with the most recently valid ramp (timeout mon-
itoring). The "ready" signal relay drops out. There is no timeout monitoring if the "acycli-
cal" transmission variant is selected.

Type

Transmission
type

Process data
length

User data

03

hex

Cyclical

2 words

Control word / speed [%] status word 1 / output current

83

hex

Acyclical

2 words

05

hex

Cyclical

3 words

Control word / speed [%] / ramp status word 1 / output
current / status word 2

85

hex

Acyclical

3 words

0

0

I