Dip switches     s2/3, Dip switches     s2/4, Dip switches     s2/5 to s2/8 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 57

Advertising
background image

Operating Instructions – MOVIMOT® MM03C - MM3XC

57

7

Description of the DIP switches S2

Startup of Standard Design

DIP switches
S2/3

Control process

DIP switches S2/3 = OFF:

VFC operation for 4-pole motors

DIP switches S2/3 = ON:

U/f operation reserved for special cases

DIP switches
S2/4

Speed monitoring

Speed monitoring (S2/4 = "ON" is used for the protection of the drive during blocking.

If the drive is operated at the current limit for more than 1 second with active speed
monitoring (S2/4 = "ON"), the speed monitoring trips. MOVIMOT

®

signals a fault via

status LED (red, flashing slowly, fault code 08). The current limit must be attained un-
interruptedly for the duration of the delay time before the monitoring function re-
sponds.

DIP switches
S2/5 to S2/8

Selection of options

Special functions can be selected using the binary coding of the DIP switches.

The possible values can be set as follows:

An overview of the selectable special functions can be found on page 58.

Decimal
Value

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

S2/5

X

X

X

X

X

X

X

X

S2/6

X

X

X

X

X

X

X

X

S2/7

X

X

X

X

X

X

X

X

S2/8

X

X

X

X

X

X

X

X

X

= ON

=

OFF

0

0

I