Operating Instructions – MOVIMOT® MM03C - MM3XC

63

7

Selectable special functions MM..C-503-00

Startup of Standard Design

Changing the
parameters in
MOVITOOLS

®

Open MOVITOOLS

®

/Shell as follows

Select "MOVIMOT

®

" equipment class [1]

Under program execution, select "Shell" [2]

After opening MOVITOOLS

®

/Shell, the following parameters are accessible. They can

be changed and stored in the unit.

The factory setting is activated as soon as special function 4 is activated via DIP
switches. If the selected special function via DIP switches remains unchanged after
switching off the 24 V operating voltage, the reactivation will use the last known val-
ues from EEPROM.

The start frequency is fixed at 0.5 Hz, the stop frequency at 3 Hz.

If the set setpoint or the maximum frequency is lower than the set minimum frequen-
cy, the minimum frequency becomes active.

The indexes are only evaluated with this special function.

05595AEN

Name

Area

Index

Parameter
number

Step width

Ramp up

0.1...1...2000 [s]

8807

130

0.1 s – 1 s:

0,01

1 s – 10 s:

0,1

10 s – 100 s:

1

100 s – 2000 s: 10

Ramp down

0.1...1...2000 [s]

8808

131

Minimum frequency

2...100 [Hz]

8899

305

0.1

Maximum frequency

1)

2...100 [Hz]

8900

306

0.1

Current limit

60...160 [%]

8518

303

1

Pre-magnetization time

0...0.4...2 [s]

8526

323

0.001

Post-magnetization time

0...0.1...2 [s]

8585

732

0.001

Parameter lock

On/Off

8595

803

Factory setting

Yes/No

8594

802

Delay time (P501/503)
Speed monitoring

0.1...1...10.0 [s]

8558

501

0.1

Brake release time

0..2 [s]

8749

731

0.001

Slip compensation

2)

0..500 [1/min]

8527

324

0.2

Factory setting = bold

1) Example: Maximum frequency = 60 Hz

Bus setpoint = 10 %
Frequency setpoint = 6 Hz

2) If the special function setting is changed, the value is set to the rated motor slip.

[1]

[2]

0

0

I