Special function 12 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 72

Advertising
background image

72

Operating Instructions – MOVIMOT® MM03C - MM3XC

7

Selectable special functions MM..C-503-00

Startup of Standard Design

Special
function 12

MOVIMOT

®

with rapid start/stop and motor protection via TH

Functional descrip-
tion

The special function is active in terminal and bus operation, but there are differences
with respect to the usable functional scope.

If the MOVIMOT

®

inverter is mounted close to the motor (with option P2.A or in the

field distributor), the special function consists of the following:

– Motor protection function via indirect TH analysis using direction of rotation termi-

nals

– Rapid start and stop function

"Motor protection
function via TH
analysis" partial
function

This function is active only in bus operation. The special function implements tripping
fault 84 "Excessive motor temperature."

Fault 84 is tripped if all of the following requirements are met:

The standard MOVIMOT

®

motor protection function can be deactivated via DIP

switch S1/5 = ON.

The direction of rotation terminals are wired to 24 V via a TH as shown in the follow-
ing figure.

The TH tripped due to excessive temperature of the motor (release of both direction
of rotation terminals does not apply).

Mains voltage is present.

06379AXX

1

6

7

8

5

4

3

2

ON

S2

6

7

8

5

With field distributor:

52119AXX

With mounting on motor
with option P2.A:

52120AXX

24V

TH

L

R

TH

24V

L

R

TH

The motor protection function via TH analysis can be deactivated by setting DIP switch
S1/5 = OFF. In this case, the motor protection in the MOVIMOT

®

that is implemented

via motor model is in effect.

0

0

I

Advertising