13 technical data with integrated as-interface, 1 iec design with connection voltages 380 vac, 1 iec design with connection voltages 380 v – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 155

Advertising
background image

Operating Instructions – MOVIMOT® MM03C - MM3XC

155

13

IEC design with connection voltages 380...500 VAC

Technical Data with Integrated AS-Interface

13

Technical Data with Integrated AS-Interface

13.1

IEC design with connection voltages 380...500 V

AC

MOVIMOT

®

type

MM 03C-

503-30

MM 05C-

503-30

MM 07C-

503-30

MM 11C-

503-30

MM 15C-

503-30

MM 22C-

503-30

MM 30C-

503-30

MM 3XC-

503-30

Part number

824 355 7

824 356 5

824 357 3

824 358 1

824 359 X

824 360 3

824 361 1

824 362 X

Apparent output power at
V

mains

= 380...500 V

AC

P

rated

1.1 kVA

1.4 kVA

1.8 kVA

2.2 kVA

2.8 kVA

3.8 kVA

5.1 kVA

6.7 kVA

Connection voltages
Permitted range

V

mains

3 x 380 V

AC

/ 400 V

AC

/ 415 V

AC

/ 460 V

AC

/ 500 V

AC

V

mains

= 380 V

AC

-10 % ... 500 V

AC

+10 %

Supply frequency

f

mains

50 Hz ... 60 Hz

±

10 %

Rated system current
(at V

mains

= 400 V

AC

)

I

mains

1.3 A

AC

1.6

A

AC

1.9

A

AC

2.4

A

AC

3.5

A

AC

5.0 A

AC

6.7 A

AC

8.6 A

AC

Output voltage

V

out

0...V

mains

Output frequency
Resolution

Operating point

f

out

2...100 Hz
0.01 Hz
400 V at 50 Hz / 100 Hz

Rated output current

I

N

1.6 A

AC

2.0

A

AC

2.5

A

AC

3.2

A

AC

4.0

A

AC

5.5 A

AC

7.3 A

AC

9.6 A

AC

Motor power S1

P

mot

0.37 kW

0.55 kW

0.75 kW

1.1 kW

1.5 kW

2.2 kW

3.0 kW

3.0 kW

Motor power S3 25 % cdf

4.0 kW

PWM frequency

4 (factory setting) / 8 / 16

1)

kHz

1) 16 kHz PWM frequency (low-noise): When DIP SWITCH S3/3 = ON, the units operate with a 16 kHz PWM frequency (low noise) and switch

back in steps to lower switching frequencies depending on the heat sink temperature.

Current limitation

I

max

Motor: 160 % with

and

Ħ

Regenerative:160 % with

and

Ħ

Maximum motor lead
length

15 m when mounting the MOVIMOT

®

frequency inverter close to the motor (with SEW hybrid

cable and option P2.A)

External braking resistor

R

min

150

68

Interference immunity

Meets EN 61800–3

Interference emission

Meets EN 61800–3 and class A limit to EN 55011 and EN 55014

Ambient temperature

ϑ

amb

-25 °C...40 °C (P

rated

reduction: 3 % I

N

per K to max. 60 °C)

2)

2) -25 °C...40 °C with S3 25% ED (up to 60 °C with S3 10 % ED)

Climate class

3 K3

Enclosure
(motor-dependent)

IP54, IP55, IP65, IP66 (options, specify when ordering)
IP67 (only available for inverters with terminal box)

Operating mode

DB (EN 60149-1-1 and 1-3), S3 max. cycle duration 10 minutes

Cooling type (DIN 41 751)

Self-cooling

Altitude

h

1000 m (P

rated

reduction: 1 % per 100 m starting at an altitude of 1000 m, see also the section

"Electrical Installation – Installation Instructions")

Power supply to control
electronics

AS-i
29.5 V - 31.6 V (AS-i power supply to EN 50295)
Optional AUX-PWR
24 V

±

25%, EN61131-2, residual ripple max. 13%, input capacitance \100

µ

F

A PELV (Protective Extra Low Voltage) power supply to IEC 60364-4-41 with safe isolation is man-
datory for the AUX-PWR auxiliary power supply.
I

E

only AS-i

200 mA

3)

(typ. 120 mA at 30 V)

I

E

AS-i + AUX-PWR

50 mA (typ. 30 mA at 30 V) + 200 mA

3)

(typ. 120 mA at 24 V)

3) The current increases by the demand of the connected sensors\ (max. 100 mA)

Control input

AS-i +
AS-i -

Connection of AS-i data line
Connection of AS-i data line

Sensor connection
(maximum sensor line length
\15 m)

Tl. DI2
Tl. DI3
Tl. 0V
Tl. 0V

External sensor input
External sensor input
24 V for sensor supply
Reference potential for sensor supply

Diagnostic interface

Modular jack 4/4 (RJ11)

P

i

f

kVA

Hz

n