Table of faults – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 128

Advertising
background image

128

Operating Instructions – MOVIMOT® MM03C - MM3XC

10

Diagnostics of MOVIMOT® standard design

Diagnostics

Table of faults

Faults

Cause / solution

Timeout of communication (motor
comes to a stop without error code)

A

Missing connection

, RS+, RS- between MOVIMOT

®

and RS-485 master.

Check the connection, in particular the ground, and repair.

B

EM interference. Check the shielding of the data cables and improve if necessary.

C

Incorrect type (cyclical) in acyclical protocol time between the individual messages.
Messages >1 s with protocol type "cyclical." Shorten message cycle or
select "acyclical."

DC link voltage too low, supply sys-
tem off detected
(motor stops, without fault code)

Check power cables and supply voltage for interruption. Motor restarts automatically as soon as
the supply voltage reaches normal values.

Fault code 01
Overcurrent of output stage

Short circuit of inverter output.
Check the connection between inverter output and motor for short circuit.
Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 06
Phase fault
(The fault can only be recognized with
a load on the drive)

Check power cables for phase fault. Reset the fault by switching off the 24 V

DC

supply voltage or

use MOVILINK

®

.

Fault code 07
DC link voltage too high

A

Ramp time too short

Increase ramp time.

B

Faulty connection between brake coil and braking resistor.

Check the connection between braking resistor and brake coil. Correct, if necessary.

C

Incorrect internal resistance of brake coil/braking resistor

Check the internal resistance of the brake coil/braking resistor

(see the section "Technical Data").

D

Thermal overload in braking resistor

Wrong size of braking resistor selected.

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 08
Speed monitoring

Speed monitoring tripped, load of drive is too high

Reduce the load of the drive.

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 11
Thermal overload of the output
stage or internal unit fault

Clean the heat sink

Reduce the ambient temperature

Prevent heat accumulation

Reduce the load on the drive

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 17 to 24, 37
CPU fault

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 25, 94
EEPROM error

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.

Fault code 84
Thermal overload of motor

With shouldered assembly of the MOVIMOT

®

inverter, set DIP switch S1/5 to "ON".

For combinations of "MOVIMOT

®

and motor with one lower power increment," check the

position of DIP switch S1/6.

Reduce the ambient temperature

Prevent heat accumulation

Reduce the load on the motor

Increasing the speed

Check the combination of the drive and MOVIMOT

®

frequency inverter if the fault is signaled

shortly after the first release.

The temperature monitoring in the motor (TH winding thermostat) has tripped with the use of
MOVIMOT

®

and selected special function 5

Reduce load on the motor.

Reset the fault by switching off the 24 V

DC

supply voltage or use MOVILINK

®

.