Coding of process data

Startup with Communications Interface / Fieldbus

Process input
data

The MOVIMOT

®

inverter sends back process input data to the master controller. The

process input data consist of status and actual value information. MOVIMOT

®

supports

the following process input data:

PI1: Status word 1

PI2: Output current

PI3: Status word 2

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Controller enable = "1"

PI1: Status word 1

Unit condition (bit 5 = "0")
0 = inverter not ready
2 = not enabled
4 = enabled

Fault number (bit 5 = "1")

Unit enabled = "1"

PO data enabled = "1"

Reserved

Reserved

Fault/warning = "1"

Reserved

Reserved

PI2: Current actual

value

16 bit integer with sign x 0.1 % I

N

Example: 0320

hex

= 800 x 0.1 % I

N

= 80 % I

N

PI3: Status word 2

(only for

three-word protocol

only)

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Controller enable = "1"

Unit enabled = "1"

PO data enabled = "1"

Reserved

Reserved

Fault/warning = "1"

Reserved

Reserved

O1 (brake)
"1" = brake applied,
"0" = brake released

O2 (ready for operation)

I1 (CW)

I2 (CCW)

I3 (setpoint f2)

Reserved 0

Reserved 0

Reserved 0

0

0

I