BECKHOFF EP2xxx User Manual

Page 152

Advertising
background image

Comissioning/Configuration

Index

Name

Meaning

Data type

Flags

Default

1C32:0

SM output
parameter

Synchronization
parameter of the
outputs

UINT8

RO

0x20 (32

dec

)

1C32:01

Sync mode

actual
synchronization
mode:

• 0: Free

Run

• 1:

Synchron
with SM 2
Event

• 2: DC­

Mode ­
Synchron
with
SYNC0
Event

• 3: DC­

Mode ­
Synchron
with
SYNC1
Event

UINT16

RW

0x0001 (1

dec

)

1C32:02

Cycle time

Cycle time (in
ns):

• Free Run:

cycle time
of the local
timer

• Synchron

with SM 2
Event:
Cycle time
of the
master

• DC­Mode:

SYNC0/
SYNC1
Cycle time

UINT32

RW

0x000F4240
(1000000

dec

)

1C32:03

Shift time

Time between
SYNC0 Event
and Outputs
Valid (in ns, only
in DC­Mode)

UINT32

RO

0x00020F58
(135000

dec

)

1C32:04

Sync modes
supported

Supported
synchronization
modes:

• Bit 0 = 1:

Free Run is
supported

• Bit 1 = 1:

Synchron
with SM 2
Event is
supported

UINT16

RO

0xC007
(49159

dec

)

EP2xxx

152

Version 2.1.0

Advertising