5 configuration – BECKHOFF EP2xxx User Manual

Page 64

Advertising
background image

Product overview

Fig. 50: EP2816­0010, DIG Outputs Device

Set safe state

Sets the module to safe state.

Reset outputs

Resets bits „Error channel X“ of the module. The outputs are activated again.

2.13.5

Configuration

A number of parameterizations can be carried out for the EP2316­0003, EP2316­0008, 2816­0008 and
2816­0010 modules on the C0E ­ Online tab in the TwinCAT System Manager.

The description of the parameterizations is done with the help of EP2316­0008 but is suitable for all this
modules.

Definitions for the behavior of the outputs in case of network failure

With bit 8000:0n (Safe State Active) you can specify that channel n should adopt a specified value (Safe
State Value) if the network communication is interrupted or not.

With bit 8001:0n (Safe State Value) you define this specific value for channel n.

Note

Safe State Value at network start up

The network transfers output process data only at the network states BOOT und Opera­
tional (OP). Also at the network states INIT, Pre­Operational (PRE­OP) and Save­Opera­
tional (SAFE­OP) passed trough during network start up no output process data is transmit­
ted. If Safe State is activated for an output, this output adopts the specified value also dur­
ing network start up.

8000:0 ­ DIG Safe state active Ch.1

Note

Observe the maximum short­circuit current!

When dimensioning the power supply unit and choosing the fuses, observe that the short­
circuit current is approximately 1.7 A.