Comissioning/Configuration

Objects for parameterization during commissioning

Index 1011 Restore default parameters

Index

Name

Meaning

Data type

Flags

Default

1011:0

Restore default
parameters

Restore the
default settings
in the EtherCAT
slave

UINT8

RO

0x01 (1

dec

)

1011:01

SubIndex 001

If this object is
set to
"0x64616F6C" ("
Set Value
Dialog") all
terminal­specific
objects are reset
to their delivery
state.

UINT32

RW

0x00000000
(0

dec

)

Index 8000 DIG Safe state active Ch.1

The outputs the bit DIG Safe state active is set for, are switched to the value that is specified in Safe state
value
, in case of status Operational (OP) is left.
Status Operational (OP) is left if communication to the master is interrupted, for example at power
breakdown at the master or cable breakage.