Product overview

8000:01 to 8000:08 ­ DIG Safe state active Ch.1, Output 1 to Output 8 (default: TRUE)

Specifies whether or not the outputs should adopt a safe state in the case of network failure.

Value

Meaning

FALSE

Safe state disabled

TRUE

Safe state enabled

8001:01 to 8001:08 ­ DIG Safe state value Ch.1, Output 1 to Output 8 (default:
FALSE)

Specifies what the safe state is.

Value

Meaning

FALSE

Output switched off

TRUE

Output switched on

Definitions for the behavior of the outputs in the presence of a short­circuit

F800:0 ­ DO Settings (Safe State Value)

Table 4: F800:01 ­ Disable shut off (default: FALSE)

Value

Meaning

FALSE

If a short­circuit occurs at one output, all outputs of
the module will be switched off.
This disabling can be removed through the process
data value Reset Outputs.

TRUE

If a short­circuit occurs at one output, only this output
of the module will be switched off.
After the short circuit has been eliminated, this output
is automatically enabled again. see "Extracted nested
table 9"

EP2xxx

73

Version 2.1.0