Definitions for the behavior of the outputs in the presence of a short­circuit

F800:0 ­ DO Settings (Safe State Value)

Fig. 22: EP2316­0008 ­ F800:0 ­ DO Settings (Safe State Value)

Table 1: F800:01 ­ Disable shut off (default: FALSE)

Value

Meaning

FALSE

If a short­circuit occurs at one output, all outputs of
the module will be switched off.
This disabling can be removed through the process
data value Reset Outputs.

TRUE

If a short­circuit occurs at one output, only this output
of the module will be switched off.
After the short circuit has been eliminated, this output
is automatically enabled again. see "Extracted nested
table 3"

F800:11 ­ Switch off time (default: 0x03E8, 1000

dec

)

Enter here the time in milliseconds after which (if F800:01 Disable shut off = FALSE) the module checks, by
switching itself on again, whether the short­circuit has been rectified.
Default = 1000 ms