2 ep2308, ep2318 - technical data – BECKHOFF EP2xxx User Manual

Page 23

Advertising
background image

Product overview

2.6.2

EP2308, EP2318 ­ Technical Data

Technical data

EP2308­0001

EP2308­0002

EP2318­0001

EP2318­0002

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of inputs

4

Input connections [

}

 98]

M8

M12

M8

M12

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

3.0 ms

3.0 ms

10 µs

10 µs

"0" signal voltage

­3...+5 V (EN 61131­2, Type 3)

"1" signal voltage

+11...+30 V (EN 61131­2, Type 3)

Input current

typically 3 mA (EN 61131­2, Type 3)

Sensor supply

derived from control voltage, max. 0.5 A total, short­circuit proof

Number of outputs

4

Output connections [

}

 95]

M8

M12

M8

M12

Load type

ohmic, inductive, lamp load

Rated output voltage

24 V

DC

 (­15%/+20%)

Output current

max. 0.5 A each channel

Short circuit current

max. 1.5 A

Module electronic supply

derived from control voltage Us

Module electronic current
consumption

typically 120 mA

Output driver supply

derived from load voltage Up

Output driver current consumption

typically 8 mA per channel

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

4 input bits, 4 output bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature
during operation

­25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)
0°C ... +55°C (according to ATEX, see special conditions [

}

 92])

Permissible ambient temperature
during storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE, cULus, ATEX

EP2xxx

23

Version 2.1.0

Advertising