Mounting and cabling

3.3.3

Power cables

Ordering data

Order designation

Power lead

Screw­in
connector

Contacts

Cross­section Length

ZK2020­3200­0020

Straight socket, open end

M8

4­pin

0.34 mm

2

2.00 m

ZK2020­3200­0050

5.00 m

ZK2020­3200­0100

10.00 m

ZK2020­3400­0020

Angled socket, open end

2.00 m

ZK2020­3400­0050

5.00 m

ZK2020­3400­0100

10.00 m

ZK2020­3132­0001

Straight socket, straight
socket

0.15  m

ZK2020­3132­0005

0.50 m

ZK2020­3132­0010

1.00 m

ZK2020­3132­0020

2.00 m

ZK2020­3132­0050

5.00 m

ZK2020­3334­0001

Angled socket, angled
socket

0.15 m

ZK2020­3334­0005

0.50 m

ZK2020­3334­0010

1.00 m

ZK2020­3334­0020

2.00 m

ZK2020­3334­0050

5.00 m

Further available power cables may be found in the Beckhoff catalog or on our internet pages (http://
www.beckhoff.com).

Technical data

Technical data

Rated voltage according to IEC60 664­1

60 V

AC

 / 75 V

DC

Contamination level according to IEC 60 664­1

3/2

Insulation resistance IEC 60 512­2

>10

9

W

Current carrying capacity according to IEC 60512­3

4 A

Volume resistance according to IEC 60512­2

< 5 mW

Protection class according to IEC 60529

IP65/66/67, when screwed together

Ambient temperature

­30°C to +80°C

3.3.4

Power cable conductor losses

The ZK2020­xxxx­yyyy power cables should not exceed the total length of 15 m at 4 A (with continuation).
When planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer
be assured if the voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must
also be taken into account.

EP2xxx

90

Version 2.1.0