Mounting and cabling

In some of the analog modules the sensors or actuators are supplied by Up ­ this means, for instance, that in
the case of 0...10 V inputs, any reference voltage (0...30 V) may be connected to Up; this is then available to
the sensors (e.g. smoothed 10 V for measuring potentiometers).

Details of the power supply may be taken from the specific module descriptions.

Attention

Electrical isolation may be cancelled!

If digital and analog fieldbus boxes are connected directly via four­core power leads, the
analog signals in the fieldbus boxes may be no longer electrically isolated from the control
voltage!

3.3.2

Status LEDs for power supply

Fig. 83: Status LEDs for power supply

LED display

LED

Display

Meaning

Us (Control voltage)

off

The power supply voltage Us is not present

green illuminated

The power supply voltage Us is present

reed illuminated

Because of overload (current > 0.5 A) the sensor supply
generated from power supply voltage Us was switched off for
all sensors fed from this.

Up (Auxiliary voltage)

off

The power supply voltage Up is not present

green illuminated

The power supply voltage Up is present

EP2xxx

89

Version 2.1.0