3 ep2809 - technical data, 4 ep2809-0021 - process image – BECKHOFF EP2xxx User Manual

Page 49

Advertising
background image

Product overview

2.11.3

EP2809 ­ Technical data

Technical data

EP2809­0021

EP2809­0022

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of outputs

16

Output connections [

}

 95]

M8

M12

Load type

ohmic, inductive, lamp load

Rated output voltage

24 V

DC

 (­15%/+20%)

Output current

max. 0.5 A each channel, total current of all outputs max. 4 A

Short circuit current

max. 4.0 A

Module electronic supply

derived from control voltage Us

Module electronic current consumption

typically 120 mA

Output driver supply

derived from load voltage Up

Output driver current consumption

typically 20 mA

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

16 output bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature during
operation

­25°C ... +60°C

­25°C ... +60°C
0°C ... +55°C (according to cULus,
see UL Requirements)

Permissible ambient temperature during
storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE

CE, cULus

2.11.4

EP2809­0021 ­ Process image

Channel 1 to Channel 16

You will find the 16 digital outputs to the module (here using the EP2809­0021 as an example) under
Channel 1 to Channel 16.

EP2xxx

49

Version 2.1.0

Advertising