BECKHOFF EP2xxx User Manual

Page 156

Advertising
background image

Comissioning/Configuration

Index

Name

Meaning

Data type

Flags

Default

1C33:0

SM input
parameter

Synchronization
parameter of the
inputs

UINT8

RO

0x20 (32

dec

)

1C33:01

Sync mode

actual
synchronization
mode:

• 0: Free

Run

• 1:

Synchron
with SM 3
Event (no
Outputs
available)

• 2: DC ­

Synchron
with
SYNC0
Event

• 3: DC ­

Synchron
with
SYNC1
Event

• 34:

Synchron
with SM 2
Event
(Outputs
available)

UINT16

RW

0x0022 (34

dec

)

1C33:02

Cycle time

same as 1C32:02
[

}

 151]

UINT32

RW

0x000F4240
(1000000

dec

)

1C33:03

Shift time

time between
SYNC0­Event
and Input Latch
(in ns, only in
DC­Mode)

UINT32

RO

0x00000000
(0

dec

)

1C33:04

Sync modes
supported

Supported
synchronization
modes:

• Bit 0: Free

Run is
supported

• Bit 1:

Synchron
with SM 2
Event is
supported
(Outputs
available)

• Bit 1:

Synchron
with SM 3
Event is
supported

UINT16

RO

0xC007
(49159

dec

)

EP2xxx

156

Version 2.1.0