2 ep2338 - technical data, 3 ep2338-000x - process image – BECKHOFF EP2xxx User Manual

Page 37

Advertising
background image

Product overview

2.8.2

EP2338 ­ Technical Data

Technical data

EP2338­0001

EP2338­0002

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of outputs

8 to 0

Output connections [

}

 95]

M8

M12

Load type

ohmic, inductive, lamp load

Rated output voltage

24 V

DC

 (­15%/+20%)

Output current

max. 0.5 A each channel

Short circuit current

max. 1.5 A

Module electronic supply

derived from control voltage Us

Module electronic current consumption

typically 120 mA

Output driver supply

derived from load voltage Up

Output driver current consumption

typically 20 mA

Number of inputs

0 to 8

Input connections [

}

 98]

M8

M12

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

10 µs

"0" signal voltage

­3...+5 V (EN 61131­2, Type 3)

"1" signal voltage

+11...+30 V (EN 61131­2, Type 3)

Input current

typically 3 mA (EN 61131­2, Type 3)

Sensor supply

derived from auxiliary voltage Up, max. 0.5 A total, short­circuit
proof

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

8 input bits, 8 output bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature during
operation

­25°C ... +60°C
0°C ... +55°C (according to cULus, see UL Requirements)
0°C ... +55°C (according to ATEX, see special conditions [

}

 92])

Permissible ambient temperature during
storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Installation position

variable

Approvals

CE, cULus, ATEX

2.8.3

EP2338­000x ­ Process image

DI Inputs

You will find the 8 digital inputs to the module (here using the EP2338­0001 as an example) under Channel
1
 to Channel 8.

EP2xxx

37

Version 2.1.0

Advertising