3 ep2316-000x - technical data – BECKHOFF EP2xxx User Manual

Page 28

Advertising
background image

Product overview

2.7.3

EP2316­000x ­ Technical Data

Technical data

EP2316­0003

EP2316­0008

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 socket (green)

Number of inputs

8

Input connections

ZS2001 Connector [

}

 99]

25 pin SUB‐D socket ﴾pins 1 ‐
8﴿ [

}

 98]

Nominal input voltage

24 V

DC

 (­15%/+20%)

Input filter

10 µs

"0" signal voltage

­3...+5 V (EN 61131­2, Type 3)

"1" signal voltage

+11...+30 V (EN 61131­2, Type 3)

Input current

typically 3 mA (EN 61131­2, Type 3)

Sensor supply

derived from control voltage, max. 0.5 A total, short­circuit
proof

Number of outputs

8

Output connections

ZS2001 Connector [

}

 99]

25 pin SUB‐D socket ﴾pins 9 ‐
18﴿ [

}

 98]

Load type

ohmic, inductive, lamp load

Rated output voltage

24 V

DC

 (­15%/+20%)

Output current

max. 0.5 A each channel, individually short­circuit proof, total
current of all outputs max. 4 A

Short circuit current

max. 1.5 A

Module electronic supply

derived from control voltage Us

Module electronic current consumption

typically 120 mA

Output driver supply

derived from load voltage Up

Output driver current consumption

max. 30 mA for all channels

Power supply connection

Feed: 1 x M8 plug, 4­pin
Onward connection: 1 x M8 socket, 4­pin

Process image

Process
data

8 input bits, 8 output bits

Diagnostic 8 diagnostic input bits

Electrical isolation

Control voltage/fieldbus: yes

Permissible ambient temperature during
operation

­25°C ... +60°C

­25°C ... +60°C
0°C ... +55°C (according to
cULus, see UL Requirements)

Permissible ambient temperature during
storage

­40°C ... +85°C

Vibration / shock resistance

conforms to EN 60068­2­6 / EN 60068­2­27

EMC resistance/emission

conforms to EN 61000­6­2 / EN 61000­6­4

Protection class

IP20

IP65, IP66, IP67 (conforms to
EN 60529)

Installation position

variable

Approvals

CE

CE, cULus

EP2xxx

28

Version 2.1.0

Advertising