2 ep2028-0032 - technical data, 3 ep2028-00xx - process image – BECKHOFF EP2xxx User Manual
Page 20
Product overview
2.5.2
EP20280032 Technical data
Technical data
EP20280032
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of outputs
8
M12
Load type
ohmic, inductive, lamp load
Rated output voltage
24 V
DC
(15%/+20%)
Output current
max. 2.8 A each channel, total current of all outputs
max. 16 A
Short circuit current
maximal 4,0 A
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Output driver supply
derived from load voltage Up
Output driver current consumption
typically 8 mA per channel
Power supply connection
Feed: 1 x 7/8" plug, 5pin
Onward connection: 1 x 7/8" socket, 5pin
Process image
8 output bits
Electrical isolation
Control voltage / fieldbus: yes
Permissible ambient temperature during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
requirements)
Permissible ambient temperature during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance / emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.5.3
EP202800xx Process image
Channel 1 to Channel 8
Under Channel 1 to Channel 8 you may find the 8 digital outputs of the module (here EP20280001 as an
example).
EP2xxx
20
Version 2.1.0