Use both parameters to adjust the characteristics of the analog input signal to terminal A1.

No.

Name

Setting Range

Default

H3-03

Terminal A1 Gain Setting

-999.9 to 999.9%

100.0%

H3-04

Terminal A1 Bias Setting

-999.9 to 999.9%

0.0%

Setting Examples

• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since

the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04

above 5 Vdc.

H3-01 = 0

10 V

5 V

0 V

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Figure 4.25 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.

0

2.0 V

10 V

100 %

Frequency
reference

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

Analog Input

Voltage

Figure 4.26 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs, the drive can automatically return to the operation it was performing prior to the power

loss based on certain conditions.

4.7 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

125