Yaskawa Z1000U User Manual

Page 165

Advertising
background image

n

H5-01: Drive Slave Address

Sets the drive slave address used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-01

Drive Slave Address

0 to FFH

1FH

Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to

be assigned in sequential order, but no two drives may share the same address.

n

H5-02: Communication Speed Selection

Sets the communications speed for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2.

Note:

1. Cycle the power after changing this parameter to enable the new setting.
2. When Metasys N2 communications are selected (H5-08 = 1), selecting a baud rate other than 9600 bps will trigger an oPE29 error.
3. When APOGEE FLN (P1) communications are selected (H5-08 = 2), selecting a baud rate other than 4800 bps will trigger an oPE29

error.

4. When BACnet communications are selected (H5-08 = 3), selecting 115200 bps (Setting 8) will trigger an oPE29 error.

No.

Name

Setting Range

Default

H5-02

Communication Speed Selection

0 to 8

<1>

<1> Default depends on H5-08 setting:

H5-08 = 0, MEMOBUS/Modbus; default: 3
H5-08 = 1, N2 (Metasys); default: 3
H5-08 = 2, P1 (APOGEE FLN); default: 2
H5-08 = 3, BACnet; default: 3

H5-02

Communication Speed

H5-02

Communication Speed

0

<1>

1200 bps

5

<1>

38400 bps

1

<1>

2400 bps

6

<1>

57600 bps

2

4800 bps

7

<1>

76800 bps

3

<1>

9600 bps

8

<1> <2>

115200 bps

4

<1>

19200 bps

<1> Not available when H5-08 is set to 2 P1 (APOGEE FLN).
<2> Not available when H5-08 is set to 0 (MEMOBUS/Modbus) or 1 (Metasys N2).

n

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

No.

Name

Setting Range

Default

H5-04

Stopping Method after CE

0 to 4

3

Setting 0: Ramp to Stop

Uses the deceleration time currently enabled.

4.12 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

165

4

Start-Up Programming & Operation

Advertising
This manual is related to the following products: