T2: parameter, T2: parameter settings during pm motor auto-tuning – Yaskawa Z1000U User Manual

Page 136

Advertising
background image

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

n

T1-03: Motor Rated Voltage

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates

above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 255.0 V

<1>

200.0 V

<1>

<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives.

n

T1-04: Motor Rated Current

Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10.0 to 150.0% of drive rated

current

Determined by

o2-04

n

T1-05: Motor Base Frequency

Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or

the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 400.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles

Sets the number of motor poles according to the motor nameplate value.

No.

Name

Setting Range

Default

T1-06

Number of Motor Poles

2 to 48

4

n

T1-07: Motor Base Speed

Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor

with an extended speed range or if using the motor in the field weakening area.

No.

Name

Setting Range

Default

T1-07

Motor Base Speed

0 to 24000 r/min

1750 r/min

n

T1-11: Motor Iron Loss

Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron

loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value

listed to T1-11 if the motor test report is available.

No.

Name

Setting Range

Default

T1-11

Motor Iron Loss

0 to 65535 W

Determined by

E2-11

n

T1-12: T1 Tuning Start

Set T1-12 to 0 to start IM Auto-Tuning.

No.

Name

Setting Range

Default

T1-12

T1 Tuning Start

0

u

T2: Parameter Settings during PM Motor Auto-Tuning

The T2-oo parameters are used to set the Auto-Tuning input data for PM motor tuning.

4.8 Auto-Tuning

136

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual