HOA Keypad Display

Fault Name

FbL

PI Feedback Loss
This fault occurs when PI feedback loss detection is programmed to trigger a fault (b5-12 = 2) and

the PI feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-13 and b5-14 settings.

Incorrect PI feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

HOA Keypad Display

Fault Name

Fdv

Power Supply Frequency Fault
The input power supply frequency exceeded the allowable frequency fluctuation.

HOA Keypad Display

Fault Name

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

Cause

Possible Solution

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

A damaged motor cable is creating a short circuit

• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.

Excessive leakage current at the drive output

• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.

The drive started to run during a current offset fault

or while coasting to a stop

• The set value exceeds the allowable setting range while the drive automatically adjusts the current

offset. This only happens when attempting to restart a PM motor that is coasting to stop.

• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.

Note:

Speed Searches 1 and 2 are the same when using OLV/PM.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

LF

Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.

Cause

Possible Solution

The output cable is disconnected

• Check for wiring errors and properly connect the output cable.
• Correct the wiring.

The motor winding is damaged

• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.

The output terminal is loose

• Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Main Circuit

Wire Gauges and Tightening Torque on page 72

for details.

The rated current of the motor being used is less

than 5% of the drive rated current

Check the drive and motor capacities.

An output transistor is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

A single-phase motor is being used

The drive cannot operate a single phase motor.

HOA Keypad Display

Fault Name

LF2

Output Current Imbalance
One or more of the phases in the output current are lost.

Cause

Possible Solution

5.4 Fault Detection

196

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual