Option installation, Prior to installing the option, Installing the option – Yaskawa Z1000U User Manual

Page 234: 4 option installation

Advertising
background image

6.4 Option Installation

This section provides instructions on installing the options in

Table 6.2

.

u

Prior to Installing the Option

Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive

functions normally without the option installed.

Table 6.2

below lists the number of options that can be connected to the drive and the drive ports for connecting those options.

Table 6.2 Option Installation

Option

Port/Connector

Number of Options Possible

AO-A3, DO-A3

CN5-A, B, C

1

SI-B3, SI-C3, SI-EN3, SI-EM3, SI-EP3, SI-ES3,

SI-ET3, SI-N3, SI-P3, SI-S3, SI-T3, SI-W3, AI-A3, DI-A3

CN5-A

1

Figure 6.2

shows an exploded view of the drive with the option and related components for reference.

C

D

F

J

K

L

M

G

H

B

A

I

E

TX

RX

ERR

RUN

A – Insertion point for CN5
B – Option card
C – Front cover
D – HOA keypad
E – LED label
F – Terminal cover
G – Included screws

H – Ground wire
I – Option modular connector
J – Drive grounding terminal (FE)
K – Connector CN5-A
L – Connector CN5-B
M – Connector CN5-C

Figure 6.2 Drive Components with Option

u

Installing the Option

Refer to the instructions below to install the option.

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or

serious injury. Before installing the option, disconnect all power to the drive. The capacitor for the control power supply remains charged

even after the power supply is turned off. The charge indicator LED will extinguish when the control power supply voltage is below 50 Vdc.

To prevent electric shock, wait at least five minutes after all indicators are off and measure the control power supply voltage level to confirm

safe level.

WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in

death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with

installation, adjustment and maintenance of AC drives and Option Cards.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option card, drive, and circuit

boards. Failure to comply may result in ESD damage to circuitry.

NOTICE: Damage to Equipment. Tighten all terminal screws to the specified tightening torque. Failure to comply may cause the application

to operate incorrectly or damage the drive.

1.

Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the HOA keypad

(E) and front covers (D, F). Front cover removal varies by model.

6.4 Option Installation

234

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

Advertising