No.

(Addr

Hex.)

Name

LCD Display

Description

Values

Page

b3-12

(019C)

Minimum Current

Detection Level during

Speed Search

Srch I Deadband

Sets the minimum current detection level during Speed Search.

Increase this setting value in increments of 0.1 if the drive fails

to perform Speed Estimation.

Default:

<1>

Min.: 2.0

Max.: 10.0

b3-14

(019E)

Bi-Directional Speed

Search Selection

Bidir Search Sel

0: Disabled

1: Enabled

0: Disabled (uses the direction of the frequency reference)

1: Enabled (drive detects which way the motor is rotating)

Default: 1

Range: 0, 1

147

b3-17

(01F0)

Speed Search Restart

Current Level

SrchRestart Lvl

Sets the Speed Search restart current level as a percentage of the

drive rated current.

Default: 150%

Min.: 0

Max.: 200

148

b3-18

(01F1)

Speed Search Restart

Detection Time

SrchRestart Time

Sets the time to detect Speed Search restart.

Default: 0.10 s

Min.: 0.00

Max.: 1.00

148

b3-19

(01F2)

Number of Speed

Search Restarts

Num of SrchRestr

Sets the number of times the drive can attempt to restart when

performing Speed Search.

Default: 3

Min.: 0

Max.: 10

148

b3-24

(01C0)

Speed Search Method

Selection

SpdSrch Method

1: CurrentDetection

2: Speed Estimation

1: Current Detection

2: Speed Estimation

Default: 2

Range: 1, 2

b3-25

(01C8) Speed Search Wait Time SpdSrch WaitTime

Sets the time the drive must wait between each Speed Search

restart attempt.

Default: 0.5 s

Min.: 0.0

Max.: 300.0

148

b3-27

(01C9)

Start Speed Search

Select

SPD Search By AI

0: start from 0

1: start SPD

Selects a condition to activate Speed Search Selection at Start

(b3-01) or External Speed Search Command 1 or 2 from the

multi-function input.

0: Triggered when a Run command is issued (normal).

1: Triggered when an external baseblock is released.

Default: 0

Range: 0, 1

b3-29

(077C)

Speed Search Induced

Voltage Level

SpdSrch Ind Vlvl

OLV/PM

OLV/PM

Performs Speed Search when the motor induced voltage

exceeds the set level.

There is normally no need to change this parameter from the

default value, but if changes are necessary, try lowering this

value in small increments. When set too low, the drive will not

perform Speed Search.

Default: 10%

Min.: 0

Max.: 10

b3-31

(0BC0)

Speed Search Operation

Current Level 1 (Current

Detection 1)

Search (I2) Lvl1

Set the current level to use to limit the output current during a

Speed Search.

Default: 1.50

Min.: 1.50

Max.: 3.50

b3-32

(0BC1)

Speed Search Operation

Current Level 2 (Current

Detection 2)

Search (I2) Lvl2

Set the current level at which to end the Speed Search for

Current Detection Type Speed Search 2.

Default: 1.20

Min.: 0.00

Max.: 1.49

b3-33

(0B3F)

Speed Search Selection

when Run Command is

Given during Uv

SpdSrch Start UV

0: Disabled

1: Enabled

Activates and deactivates Speed Search at start in accordance

with whether a Run command was issued during an

undervoltage (Uv) condition. Function is active when a

momentary power loss (L2-01 = 1 or 2), Speed Search at start

(b3-01 = 1), and coasting to a stop (b1-03 = 1) are enabled.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

b3-50

(0BC7)

Backspin Search

Direction Judgment

Time 1

Bkspin Srch Time1

Adjusts the direction of Speed Search to allow for backspin.

Default: 0.0 s

Min.: 0.0

Max.: 10.0

b3-51

(0BC8)

Backspin Search

Direction Judgment

Time 2

Bkspin Srch Time2

Default: 0.0 s

Min.: 0.0

Max.: 10.0

b3-52

(0BC9)

Backspin Search

Deceleration Time 1

BkspinSrchDecel1

Sets the search frequency deceleration rate when searching from

the direction command when the momentary power loss time is

shorter than the time set in b3-50.

Default: 2.0 s

Min.: 0.0

Max.: 10.0

b3-53

(0BCA)

Backspin Search

Deceleration Time 2

BkspinSrchDecel2

Sets the search frequency deceleration rate for a Speed Search

from the opposite direction of the direction command when the

momentary power loss time is equal to or longer than the time

set in b3-51.

Default: 2.0 s

Min.: 0.0

Max.: 10.0

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.