T2-08: Number of PM Motor Poles

Enter the number of motor poles.

No.

Name

Setting Range

Default

T2-08

Number of PM Motor Poles

2 to 48

6

n

T2-10: PM Motor Stator Resistance

Enter the motor stator resistance per motor phase.

No.

Name

Setting Range

Default

T2-10

PM Motor Stator Resistance

0.000 to 65.000 Ω

Determined by T2-02

n

T2-11: PM Motor d-Axis Inductance

Enter the d-Axis inductance per motor phase.

No.

Name

Setting Range

Default

T2-11

PM Motor d-Axis Inductance

0.00 to 600.00 mH

Determined by T2-02

n

T2-12: PM Motor q-Axis Inductance

Enter the q-Axis inductance per motor phase.

No.

Name

Setting Range

Default

T2-12

PM Motor q-Axis Inductance

0.00 to 600.00 mH

Determined by T2-02

n

T2-13: Induced Voltage Constant Unit Selection

Selects the units used for setting the induced voltage coefficient.

No.

Name

Setting Range

Default

T2-13

Induced Voltage Constant Unit Selection

0, 1

1

Setting 0: mV (r/min)
Setting 1: mV (rad/sec)

Note:

If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction

Voltage Constant 1 (Ke)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.

n

T2-14: PM Motor Induced Voltage Constant (Ke)

Enter the motor induced voltage constant (Ke).

No.

Name

Setting Range

Default

T2-14

PM Motor Induced Voltage Constant (Ke)

0.0 to 2000.0

Determined by T2-02

n

T2-15: Pull-In Current Level for PM Motor Tuning

Sets the amount of pull-in current. Set as a percentage of the motor rated current.

No.

Name

Setting Range

Default

T2-15

Pull-In Current Level for PM Motor Tuning

0 to 120%

30%

4.8 Auto-Tuning

138

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual