L9: drive protection 2 – Yaskawa Z1000U User Manual

Page 294

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-29

(04DF)

Current Unbalance

Detection (LF2)

LF2 Flt Det Sel

0: Disabled

2: Current Det Type

OLV/PM

OLV/PM

0: Disabled

2: Enabled (current detection)

Default: 2

Range: 0, 2

L8-32

(04E2)

Main Contactor and

Cooling Fan Power

Supply Failure Selection

FAN Fault Sel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

Determines drive response when a fault occurs with the internal

cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the deceleration time set

to C1-09)

Default: 1

Range: 0 to 2

172

L8-35

(04EC)

Installation Method

Selection

Installation Sel

0: IP00/OpenChassis

2: IP20/Nema Type 1

3: Finless/Fin Ext

0: IP00/Open-Chassis enclosure

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink installation

Default:

<1> <2>

<3>

Range: 0, 2, 3

172

L8-38

(04EF)

Carrier Frequency

Reduction

Fc Reduct dur OL

0: Disabled

1: Active below 6Hz

2: Active @ any Spd

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default:

<4>

Range: 0 to 2

172

L8-40

(04F1)

Carrier Frequency

Reduction Off Delay

Time

Fc Reduct Time

Sets the time that the drive continues running with reduced

carrier frequency after the carrier reduction condition is gone.

Setting 0.00 s disables the carrier frequency reduction time.

Default: 0.50 s

Min.: 0.00

Max.: 2.00

173

L8-41

(04F2)

High Current Alarm

Selection

High Cur Alm Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled.

An alarm is triggered at output currents above 150% of drive

rated current.

Default: 0

Range: 0, 1

173

L8-97

(3104)

Carrier Frequency

Reduction Selection

during oH Pre-Alarm

FC Sel dur OHAlm

0: Disabled

1: Enabled

Carrier frequency reduction protection selection. It is reduced

to the carrier frequency at oH pre-alarm.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by parameter o2-04, Drive Model Selection.
<4> Default setting is dependent on parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.

u

L9: Drive Protection 2

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L9-03

(0819)

Carrier Frequency

Reduction Level

Selection

Fc ReductLvl Sel

0: Disabled

1: Enabled

Selects the level to start the reduction of the frequency or to clear

the current frequency level for the automatic reduction of the

carrier frequency.

There is normally no need to change this parameter from the

default value.

0: Reduces the carrier frequency based on the drive rated current

that is not derated.

1: Reduces the carrier frequency based on the drive rated current

that is derated by the carrier frequency and the temperature

selected for C6-02.

Default: 0

Range: 0, 1

B.9 L: Protection Function

294

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual