Yaskawa Z1000U User Manual

Page 261

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-27

(01E9)

PID Snooze Feedback

Level

Snooze Reset Lvl

Sets the PID feedback level above which Snooze mode is

activated. Set as a percentage of the maximum frequency.

Default: 60%

Min.: 0

Max.: 100

153

b5-28

(01EA)

PID Feedback Function

Selection

PID FdbkSqrt Sel

0: Disabled

1: Enabled

0: Disabled

1: Square root

Default: 0

Range: 0, 1

153

b5-29

(01EB) PID Square Root Gain

PID FdbkSqrtGain

A multiplier applied to the square root of the feedback.

Default: 0.00

Min.: 0.00

Max.: 2.00

153

b5-30

(01EC) PID Feedback Offset

PID Fdbk Offset

PID feedback offset set as a percentage of the maximum

frequency.

Default: 0.00

Min.: 0.00

Max.: 100.00

153

b5-34

(019F) PID Output Lower Limit PID Out Low Lim

Sets the minimum output possible from the PID controller as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

153

b5-35

(01A0) PID Input Limit

PID Input Limit

Limits the PID control input (deviation signal) as a percentage

of the maximum output frequency. Acts as a bipolar limit.

Default:

1000.0%

Min.: 0.0

Max.: 1000.0

153

b5-36

(01A1)

PID Feedback High

Detection Level

Fb High Det Lvl

Sets the PID feedback high detection level as a percentage of

the maximum output frequency.

Default: 100%

Min.: 0

Max.: 100

154

b5-37

(01A2)

PID Feedback High

Detection Time

Fb High Dly Time

Sets the PID feedback high level detection delay time.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

154

b5-38

(01FE)

PID Setpoint User

Display

PID UsrDspMaxVal

Sets the display value of U5-01 and U5-04 when the maximum

frequency is output.

Default:

<2>

Min.: 1

Max.: 60000

154

b5-39

(01FF)

PID Setpoint Display

Digits

PID UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2: 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default:

<2>

Range: 0 to 3

154

b5-40

(017F)

Frequency Reference

Monitor Content during

PID

Fref Mon Sel@PID

0: Fref Mon w PID

1: Fref Mon w/o PID

0: Display the frequency reference (U1-01) after PID

compensation has been added.

1: Display the frequency reference (U1-01) before PID

compensation has been added.

Default: 0

Range: 0, 1

154

b5-41

(0160)

PID Unit Selection

PID Mon Unit Sel

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: Ft

13: LPM

14: CMM

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

Default: 0

Range: 0 to 14

154

b5-42

(0161)

PID Output Monitor

Calculation Method

PID Out Calc Mode

0: Linear

1: Square root

2: 1/f2

3: 1/f3

0: Linear - the monitor displays PID output

1: Square root - the monitor displays square root PID output

2: Quadratic - the monitor displays 1/(PID output)

3: Cubic - the monitor displays 1/(PID output)

Default: 0

Range: 0 to 3

155

b5-43

(0162)

PID Output 2 Monitor

Max Upper 4 Digits

PID Out MonMax U4

Sets the upper 4 digits of the maximum monitor value.

Used with b5-44 to set maximum monitor value of U5-14 and

U5-15 at maximum frequency.

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 9999

155

B.3 b: Application

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

261

B

Parameter List