The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to

the set value.

n

L8-40: Carrier Frequency Reduction Off-Delay Time

Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily

derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.

No.

Name

Setting Range

Default

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00 s

0.50 s

n

L8-41: High Current Alarm Selection

Triggers a high current alarm (HCA) when the output current exceeds 150% of the drive rated current.

No.

Name

Setting Range

Default

L8-41

High Current Alarm Selection

0, 1

0

Setting 0: Disabled

No alarm is detected.

Setting 1: Enabled

An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm

(H2-oo = 10) will close.

n

o1-01: Drive Mode Unit Monitor Selection

When o1-02 is set to 5, any U monitors can be displayed. This parameter will select the monitors. Pressing the up arrow key

will display the following data: frequency reference → rotational direction → output frequency → output current → o1-01

selection.
Parameter o1-01 selects the content of the last monitor in this sequence. This is done by entering the “1oo” part of
“U1-oo”. Certain monitors are not available in some control modes. There is no effect like this on an LCD operator.

No.

Name

Setting Range

Default

o1-01

Drive Mode Unit Monitor Selection

104 to 914

U1-04 (Control Mode) to

U9-14 (Power Monitor)

<1>

106 (U1-06)

<1> U2-oo and U3-oo parameters cannot be selected.

n

o1-02: User Monitor Selection after Power Up

Selects which monitor parameter is displayed upon power up by entering the 1- oo part of U1-oo. Certain monitors are

not available in some control modes.

No.

Name

Setting Range

Default

o1-02

User Monitor Selection after Power Up

1 to 5

<1>

<1> Default is 1 when b5-01 is set to 0.

Default is 3 when b5-01 is set to 1 or 3.

Setting 1: Frequency Reference (U1-01)
Setting 2: Motor Direction
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Monitor

The monitor value selected by o1-01 will be displayed.

n

o1-03: HOA Keypad Display Selection

Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting

parameters o1-10 and o1-11.

No.

Name

Setting Range

Default

o1-03

HOA Keypad Display Selection

0 to 3

0

4.12 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

173