Yaskawa Z1000U User Manual

Page 167

Advertising
background image

No.

Name

Setting Range

Default

H5-09

Communications Fault Detection Time

0.0 to 10.0 s

2.0 s

n

H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

No.

Name

Setting Range

Default

H5-10

Unit Selection for MEMOBUS/Modbus Register 0025H

0 or 1

0

Setting 0: 0.1 V units
Setting 1: 1 V units

n

H5-11: Communications Enter Function Selection

Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.

Refer

to Enter Command on page 335

.

No.

Name

Setting Range

Default

H5-11

Communications Enter Function Selection

0 or 1

0

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter

change, not for each single parameter.

Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n

H5-12: Run Command Method Selection

Selects the type of sequence used when the Run command source is set to network communications (b1-02 = 2).
When BACnet protocol is selected (H5-08 = 3), then the value entered for H5-12 will be ignored and the logic will be handled

as though “0” was entered (FWD/Stop, REV/Stop method).

No.

Name

Setting Range

Default

H5-12

Run Command Method Selection

0 or 1

0

Setting 0: FWD/Stop, REV/Stop

Setting bit 0 will start and stop the drive in the forward direction. Setting bit 1 will start and stop the drive in reverse.

Setting 1: Run/Stop, FWD/REV

Setting bit 0 will start and stop the drive. Setting bit 1 changes the direction.

n

L5-02: Auto Restart Fault Output Operation Selection

Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.

No.

Name

Setting Range

Default

L5-02

Auto Restart Fault Output Operation Selection

0, 1

0

Setting 0: No Fault Output
Setting 1: Fault Output Is Set

n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

No.

Name

Setting Range

Default

L5-04

Fault Reset Interval Time

0.5 to 600.0 s

10.0 s

n

L5-05: Fault Reset Operation Selection

No.

Name

Setting Range

Default

L5-05

Fault Reset Operation Selection

0, 1

1

4.12 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

167