U1: operation status monitors, U2: fault trace, U3: fault history – Yaskawa Z1000U User Manual

Page 180: U4: maintenance monitors

Advertising
background image

No.

Name

Setting Range

Default

T1-06

Number of Motor Poles

2 to 48

4

n

T1-07: Motor Base Speed

Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor

with an extended speed range or if using the motor in the field weakening area.

No.

Name

Setting Range

Default

T1-07

Motor Base Speed

0 to 24000 r/min

1750 r/min

n

T1-11: Motor Iron Loss

Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron

loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value

listed to T1-11 if the motor test report is available.

No.

Name

Setting Range

Default

T1-11

Motor Iron Loss

0 to 65535 W

Determined by

E2-11

n

T1-12: T1 Tuning Start

Set T1-12 to 0 to start IM Auto-Tuning.

No.

Name

Setting Range

Default

T1-12

T1 Tuning Start

0

u

U1: Operation Status Monitors

Status monitors display drive status data such as output frequency and output current.

Refer to U1: Operation Status

Monitors on page 309

for a complete list of U1-oo monitors and descriptions.

u

U2: Fault Trace

Use these monitor parameters to view the status of various drive aspects when a fault occurs.
This information is helpful for determining the cause of a fault.

Refer to U2: Fault Trace on page 311

for a complete list of

U2-oo monitors and descriptions.
U2-oo monitors are not reset when the drive is initialized.

Refer to o4-11: U2, U3 Initialization on page 178

for instructions

on how to reset these monitor values.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U3: Fault History

These parameters display faults that have occurred during operation as well as the drive operation time when those faults

occurred.

Refer to U3: Fault History on page 312

for a complete list of U3-oo monitors and descriptions.

U3-oo monitors are not reset when the drive is initialized.

Refer to o4-11: U2, U3 Initialization on page 178

for instructions

on how to reset these monitor values.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U4: Maintenance Monitors

Maintenance monitors show:
• Runtime data of the drive and cooling fans and number of Run commands issued
• Maintenance data and replacement information for various drive components
• kWh data
• Highest peak current that has occurred and output frequency at the time the peak current occurred
• Motor overload status information
• Detailed information about the present Run command and frequency reference source selection

4.12 Advanced Drive Setup Adjustments

180

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual