Yaskawa Z1000U User Manual

Page 188

Advertising
background image

u

Parameters to Minimize Motor Hunting and Oscillation

In addition to the parameters discussed on pages

186

and

187

, parameters in

Table 5.3

indirectly affect motor hunting and

oscillation.

Table 5.3 Parameters that Affect Control Performance in Applications

Name

(Parameter No.)

Application

Accel/Decel Time

(C1-01 through C1-11)

Adjusting accel and decel times will affect the torque presented to the motor during acceleration or deceleration.

S-Curve Characteristics

(C2-01 and C2-02)

Prevents shock at the beginning and end of acceleration and deceleration.

Jump Frequency

(d3-01 through d3-04)

Skips over the resonant frequencies of connected machinery.

Analog Filter Time Constant

(H3-13)

Prevents fluctuation in the analog input signal due to noise.

Stall Prevention

(L3-01 through L3-06)

• Prevents motor speed loss and overvoltage when the load is too heavy or during sudden acceleration/

deceleration.

• Adjustment is not normally necessary because Stall Prevention is enabled as a default.

5.2 Motor Performance Fine-Tuning