Three-phase 200 v class, Three-phase 400 v class – Yaskawa Z1000U User Manual

Page 28

Advertising
background image

CIMR - Z U 4

E

A

0096

U A

Z1000U
Series

No.

Enclosure

Type

Design

Revision

Order

No.

Region

Code

U

USA

IP00

A

No.

Voltage Class

No.

Environmental

Specification

3-phase, 380-480 Vac

3-phase, 200-240 Vac

2

4

<1>

U

Humidity and dust
resistant

No.

Customized

Specifications

E

Without EMC

Noise Filter

Built-in EMC

Noise Filter

U

Figure 1.2 Drive Model Number Definition

<1> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.

n

Three-Phase 200 V Class

Table 1.3 Model Number and Specifications (200 V Class)

Drive Model

Reference Motor

Capacity kW (HP)

Rated Output

Current A

2o0028

7.5 (10)

28

2o0042

11 (15)

42

2o0054

15 (20)

54

2o0068

18.5 (25)

68

2o0081

22 (30)

81

Drive Model

Reference Motor

Capacity kW (HP)

Rated Output

Current A

2o0104

30 (40)

104

2o0130

37 (50)

130

2o0154

45 (60)

154

2o0192

55 (75)

192

2o0248

75 (100)

248

n

Three-Phase 400 V Class

Table 1.4 Model Number and Specifications (400 V Class)

Drive Model

Reference Motor

Capacity kW (HP)

Rated Output

Current A

4o0011

5.5 (7.5)

11

4o0014

7.5 (10)

14

4o0021

11 (15)

21

4o0027

15 (20)

27

4o0034

18.5 (25)

34

4o0040

22 (30)

40

4o0052

30 (40)

52

4o0065

37 (50)

65

4o0077

45 (60)

77

Drive Model

Reference Motor

Capacity kW (HP)

Rated Output

Current A

4o0096

55 (75)

96

4o0124

75 (100)

124

4o0156

90 (125)

156

4o0180

110 (150)

180

4o0216

132 (175)

216

4o0240

150 (200)

240

4o0302

185 (250)

302

4o0361

220 (300)

361

4o0414

260 (350)

414

1.3 Model Number and Nameplate Check

28

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

Advertising
This manual is related to the following products: