The function triggered by parameter b2-01 depends on the control mode that has been selected.

V/f and OLV/PM (A1-02 = 0, 5)

For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output

frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.

Output

frequency

Time

b2-04

DC Injection

Braking

E1-09 Min. Frequency
b2-01 Zero Speed Level

Figure 4.30 DC Injection Braking at Stop for V/f

Note:

If b2-01 is set to a smaller value than E1-09 (Minimum Output Frequency), then DC Injection Braking will begin when the frequency falls

to the E1-09 value.

n

b2-02: DC Injection Braking Current

Sets the DC Injection Braking current as a percentage of the drive rated current.

No.

Name

Setting Range

Default

b2-02

DC Injection Braking Current

0 to 100%

50%

The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.

Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher

than the level necessary to hold the motor shaft.

n

b2-03: DC Injection Braking Time at Start

Sets the time of DC Injection Braking at start. Used to stop a coasting motor before restarting it or to apply braking torque at

start. Disabled when set to 0.00 s.

No.

Name

Setting Range

Default

b2-03

DC Injection Braking Time at Start

0.00 to 10.00 s

0.00 s

Note:

Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the

motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.

n

b2-03: DC Injection Braking Time at Start

Sets the time of DC Injection Braking at start. Used to stop a coasting motor before restarting it or to apply braking torque at

start. Disabled when set to 0.00 s.

No.

Name

Setting Range

Default

b2-03

DC Injection Braking Time at Start

0.00 to 10.00 s

0.00 s

Note:

Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the

motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

Determined by

A1-02

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search

is complete.

4.12 Advanced Drive Setup Adjustments

146

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual