Alarm (alm) led displays, Auto led and hand led indications, Lit while the drive is in hand mode – Yaskawa Z1000U User Manual

Page 97: 2 using the hoa keypad

Advertising
background image

No.

Name

Display

Content

9

Function Key 2

(F2)

FWD/REV Pressing

F2

switches between forward and reverse.

DATA

Pressing

F2

scrolls to the next display.

Pressing

F2

scrolls the cursor to the right.

RESET

Pressing

F2

resets the existing drive fault error.

Monitor

Pressing

F2

switches Monitor mode.

DRV/BYP The multi-function relay selected Drive/Bypass contact will be toggled.

RUNBYP The multi-function relay selected to RUN Bypass will be toggled.

RLY

The multi-function relay selected to Relay operator control will be toggled.

<1> Displayed when in Frequency Reference Mode.
<2> Displayed when in Frequency Reference Mode and Monitor Mode.

u

ALARM (ALM) LED Displays

Table 4.2 ALARM (ALM) LED Status and Contents

State

Content

Display

Illuminated

When the drive detects an alarm or error.

Flashing

• When an alarm occurs.
• When an oPE is detected.
• When a fault or error occurs during Auto-Tuning.

Off

Normal operation (no fault or alarm).

u

AUTO LED and HAND LED Indications

Table 4.3 AUTO LED and HAND LED Indications

AUTO LED

HAND LED

State

AUTO

Off

HAND

Off

OFF mode

AUTO

Off

HAND

On solid

HAND mode

AUTO

Off

HAND

Long blink (50% duty)

HAND mode when the Frequency Reference is 0 and/or decelerating in HAND mode.

AUTO

On solid

HAND

Off

Running in AUTO mode

AUTO

Long blink (50% duty)

HAND

Off

Running in AUTO mode when the Frequency Reference is 0 and/or decelerating in AUTO

mode.

AUTO

Short blink (15% duty)

HAND

Off

AUTO mode, Ready, No run command input.

AUTO

Double blink

HAND

Off

AUTO mode, stopped by a Fast- Stop from a Multi-Function Digital Input.

4.2 Using the HOA Keypad

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

97

4

Start-Up Programming & Operation

Advertising
This manual is related to the following products: