5.10 Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.

Refer to Motor

Performance Fine-Tuning on page 186

for guidance on troubleshooting.

• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise

u

Common Problems

Common Problems

Page

Cannot Change Parameter Settings

220

Motor Does Not Rotate Properly after Pressing RUN Button or after

Entering External Run Command

Motor Does Not Rotate

221

Motor Rotates in the Opposite Direction from the Run Command

222

Motor Rotates in One Direction Only

222

Motor is Too Hot

222

Drive Does Not Allow Selection of Rotational Auto-Tuning

223

oPE02 Error Occurs When Lowering the Motor Rated Current Setting

223

Motor Stalls During Acceleration or With Large Loads

223

Drive Frequency Reference Differs from the Controller Frequency Reference Command

224

Excessive Motor Oscillation and Erratic Rotation

224

Noise From Drive or Motor Cables When the Drive is Powered On

225

Ground Fault Circuit Interrupter (GFCI) Trips During Run

225

Connected Machinery Vibrates When Motor Rotates

Unexpected Noise from Connected Machinery

225

Oscillation or Hunting

225

PID Output Fault

226

Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)

226

Output Frequency is not as High as Frequency Reference

226

Buzzing Sound from Motor at 2 kHz

226

Unstable Motor Speed when Using PM or IPM

226

Motor Does Not Restart after Power Loss

227

The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals DM+ and DM-)

227

u

Cannot Change Parameter Settings

Cause

Possible Solutions

The drive is running the motor

(i.e., the Run command is present).

• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.

The Access Level is set to restrict access to parameter

settings.

• Set the Access Level to allow parameters to be edited (A1-01 = 2).

The operator is not in the Parameter Setup Mode

(the screen will display “PAr”).

• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”

appears on the screen.

Refer to The Drive, Programming, and Clock Adjustment Modes on

page 100

.

A multi-function contact input terminal is set to allow

or restrict parameter editing

(H1-01 through H1-08 = 1B).

• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.

5.10 Troubleshooting without Fault Display