Phase loss has occurred on the output side of the

drive

• Check for faulty wiring or poor connections on the output side of the drive.
• Correct the wiring.

Terminal wires are loose on the output side of the

drive

Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Main Circuit

Wire Gauges and Tightening Torque on page 72

for details.

The output circuit is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Motor impedance or motor phases are uneven

• Measure the line-to-line resistance for each motor phase. Ensure all values match.
• Replace the motor.

HOA Keypad Display

Fault Name

nSE

Node Setup Error
A terminal assigned to the node setup function closed during run.

Cause

Possible Solution

The node setup terminal closed during run

Stop the drive when using the node setup function.

A Run command was issued while the node setup

function was active

HOA Keypad Display

Fault Name

oC

Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.

Cause

Possible Solution

The motor has been damaged due to overheating

or the motor insulation is damaged

• Check the insulation resistance.
• Replace the motor.

One of the motor cables has shorted out or there is

a grounding problem

• Check the motor cables.
• Remove the short circuit and reapply power to the drive.
• Check the resistance between the motor cables and the ground terminal .
• Replace damaged cables.

The load is too heavy

• Measure the current flowing into the motor.
• Replace the drive with a larger capacity drive if the current value exceeds the rated current.
• Determine if there is sudden fluctuation in the current level.
• Reduce the load to avoid sudden changes in the current level or switch to a larger drive.

The acceleration or deceleration times are too short

Calculate the torque needed during acceleration relative to the load inertia and the specified

acceleration time. If it is not possible to set the proper amount of torque, make the following changes:
• Increase the acceleration time (C1-01 and C1-03)
• Increase the S-curve characteristics (C2-01 and C2-02)
• Increase the capacity of the drive.

The drive is attempting to operate a specialized

motor or a motor larger than the maximum size

allowed

• Check the motor capacity.
• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on

the motor nameplate.

Magnetic contactor (MC) on the output side of the

drive has turned on or off

Set up the operation sequence so the MC does not trip while the drive is outputting current.

V/f setting is not operating as expected

• Check the ratios between the voltage and frequency.
• Set parameters E1-04 through E1-10 appropriately.
• Lower the voltage if it is too high relative to the frequency.

Excessive torque compensation

• Check the amount of torque compensation.
• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.

Drive fails to operate properly due to noise

interference

• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference and check the control circuit lines, main circuit

lines, and ground wiring.

Overexcitation gain is set too high

• Check if the fault occurs simultaneously with overexcitation function operation.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).

Run command was applied while motor was

coasting

• Set b3-01 to 1 to enable Speed Search at Start.
• Program the Speed Search command input through one of the multi-function contact input terminals

(H1-oo = 61 or 62).

The motor control method and motor do not match

• Check the control mode.
• For IM motors, set A1-02 to 0.
• For PM motors, set A1-02 to 5.